MAIN FEATURES
- Flex-PPs series, polypropylene flexible single wall;
- PPs rigid series
- Polypropylene rigid single wall, in white colour;
- Product certified for condensation generators (T120°)
- EN 14241-1 certified sealing ring;
- Complete range;
Material specification | |
Inside diameter(mm): | 60•80•110•125•160•200•250•315 |
Inner surface | 1.5 mm minimum nominal thickness Homopolymer polypropylene quality |
Surface thermal resistance m2K/W at 200°C | Without insulation = 0.00 |
Sealing ring | Profiled ring seal with three black silicone sealing lips conforming to UNI EN 14241/1 |
Roughness | 1 mm average value |
General information | |
Installation | Internal Yes External NO it is neither rain nor UV ray proof |
Fields of application | Ducts, chimneys, smoke ducts, manifolds and flues connected to blown air, atmospheric, condensation and pressurised boilers, type B and C appliances, condensation, kitchen hoods, ovens and ventilation ducts |
Permitted fuels | T120 Gas, LPG and Diesel oil with a sulphur content =0.2% in mass |
Conservation | In environments with a non-corrosive atmosphere |
Product warranty | As per the 99/44/EC directive |
Dangerous substances | None |
Freezing-thawing resistance | Requirement not met |
Accidental contact | Protective shields must be used when surface temperature is greater than 70°C |
Storage | Do not store the material near ferrous materials, premises must be dry and protected against the elements |
Usage limits | Environments such as laundries, dyeworks, furrier’s, print shops, beauty salons or places with halogenated or chromate vapors |
Product designation as per the EN 1447-1 standard | Chimney system |
No. of the standard | EN 1447-1 |
Temperature level | T120 |
Pressure level | P1/H1 |
Resistance to condensation | W |
Resistance to corrosion | 2 |
Place of installation | I |
Resistance to fire from inside and distance from combustible materials | O(20) |
Reaction to fire | D |
Wall class | L |
Performance required according to the designation | ||
Temperature level | T120 | working with a nominal fumes temperature at less than 120°C |
Pressure level | P1
H1 |
working with a positive and negative pressure up to 200Pa. Permitted loss less than 0.006 l/m2 working with a positive and negative pressure up to 5000Pa. Permitted loss less than 0.006l/sm2 |
Resistance to condensation | W | working with moist and dry fumes |
Resistance to corrosion | V2 | working with Gas, LPG and Diesel oil with a sulphur content ≤ 0.2% in mass |
Place of installation | I | only inside buildings |
Reaction to fire | D | on a scale that goes from F (products that cannot be classified as fire resistant) to A1 (products that in no way contribute to any phases of a fire). Class D are products that can resist the action of a small flame for a short length of time with no substantial spreading of the fire. |
Wall class | L | no external protection |
Resistance to fire from inside | O | not fire resistant from inside |
Distance from combustible materials | (20) | (20)=minimum 20mm; |
INSTALLATION INSTRUCTIONS
- Position the elements with the female socket facing up.
- Use the sliding element for the male-female connection and always maintain a 3° slanting angle on horizontal installations.
- Observe the compression loads and the non-vertical installations.
ESSENTIAL FEATURES
Resistance to the wind load:
- Distance between wall brackets: NPD m
- Free length from the last bracket: 3 m
Compressive strength:
- Linear elements’ maximum load: 30m
- Maximum load of a straight fitting at 90°: 30m
- Maximum load of the wall chimney support
30m Tensile and bending strength (linear elements):
- Maximum load at traction (element connection means and chimney connections): NPDm
- Non-vertical installations: NPD
- Non-vertical installations: distance between wall chimney supports = NPD
Traction and bending strength (non-linear elements):
- Non-vertical installations: NPD
FLUE SYSTEM MAINTENANCE
Scheduled maintenance carried out by qualified personnel:
- Unless standards dictate otherwise or different agreements are reached with the user, the following maintenance schedule is advisable:
- gaseous fuels: 1 / year;
- liquid fuels: 1 / 6 months;
- Clean the smoke duct with a soft plastic brush or sponge as well as the equipment compartment for pipe supply and ventilation, the inspection fitting and chimney and also make sure the smoke/fumes and condensates etc., are flowing freely.