Condensation in Polypropylene.

Technical Data
Material specification:
Internal diameter (mm): 50•60•80•100•125•160•200•250•315
Inner wallMinimum nominal thickness: 1.5mm

Homopolymer polypropylene quality

Wall thermal resistance m²K/W at 200°C:
Without insulation = 0.00
Sealing ring: Profiled ring gasket with three sealing lips in black silicone, compliant with UNI EN 14241-1
Roughness: average value 1 mm
General information
InstallationInternal: Yes

External: NO, does not resist rainwater penetration and UV rays.

Applications: Ducts, chimneys, flue channels, collectors, and chimneys connected to forced-air, atmospheric, pressurized boilers, type B, C appliances, condensing units, kitchen hoods, ovens, and ventilation ducts.
Allowed fuels: T120 Gas, LPG, and Diesel with a sulfur content of =0.2% by mass.
Storage: In environments where the atmosphere is non-corrosive
Product warranty: In accordance with Directive 99/44/EC
Hazardous substances: None
Frost – Thaw resistance: Requirement not met.
Accidental contact: Protective shielding is required when the wall surface temperature exceeds 70°C
Storage: Do not store the material near ferrous materials; environments must be dry and protected from weather exposure
Usage limits: Environments such as laundries, dry cleaners, furriers, printing shops, cosmetic salons, or places where halogen or chromate vapors are present.
Product designation according to the EN 1447-1 standard: Chimney system.
The number of the standard is EN 1447-1.
Temperature level: T120.
Pressure level: P1/H1.
Condensate resistance
W
Corrosion resistance: 2.
Luogo di installazioneI
Fire resistance from the inside and distance from combustible materials: O(20).
Fire reaction: D.
Wall class: L.

Performance requirements according to the designation
Temperature level T120 — operation with a nominal flue gas temperature below 120 °C.
Pressure levelP1

H1

Operation with positive and negative pressure up to 200 Pa.
Permissible leakage less than 0.006 l/m²

Operation with positive and negative pressure up to 5000 Pa. Acceptable leakage less than 0.006 l/sm².

Operation with positive and negative pressure up to 5000 Pa. Acceptable leakage less than 0.006 l/sm².
Corrosion resistance: V2.
Operation with Gas, LPG, and Diesel with a sulfur content ≤ 0.2% by mass.
Installation location: Isolated inside buildings.
Fire reaction: D. The scale ranges from F (products that cannot be classified as fire-resistant) to A1 (products that do not contribute to any phase of the fire). Class D products can withstand a small flame for a short period without substantial propagation.
Wall class: L, without external protection.
Fire resistance from the inside: O, does not resist fire from the inside.
Distance from combustible materials: (20)(20) = minimum 20mm.

INSTALLATION INSTRUCTIONS

  • Place the elements with the female socket facing upwards.
  • Use the appropriate sliding connector for the male-female joint, and for horizontal installations, always maintain an inclination of 3°.
  • Respect compression loads and non-vertical installation requirements.

ESSENTIAL CHARACTERISTICS

Wind load resistance:

  • Distance between wall brackets: NPD m
  • Free length from the last bracket: 3 meters.

Compression resistance:

  • Maximum load for linear elements: 30 meters.
  • Maximum load for 90° straight connector: 30 meters.
  • Maximum load for wall-mounted chimney support: 30 meters.

Tensile and bending resistance (straight elements):

  • Maximum tensile load (means of connection of elements and chimney fittings): NPDm.
  • Non-vertical installations: NPD
  • Non-vertical installations: distance between wall chimney supports = NPD (No Performance Determined)

Tensile and bending resistance (non-linear elements):

  • Non-vertical installations: NPD

FLUE SYSTEM MAINTENANCE

Scheduled maintenance carried out by qualified personnel:

  • Unless otherwise required by regulations or agreed with users, the following maintenance intervals are recommended:
    • Gaseous fuels: once per year;
    • Liquid fuels: once every 6 months;
  • Cleaning using a soft plastic brush or sponge of the flue pipe, the technical compartment for air supply and ventilation of the ducts, the inspection connection, the chimney cap; checking the free flow of flue gases and condensate, etc.

Contact us

Request information or a customized quote

"*" indicates required fields

Dati personali*

Lasciaci il tuo numero di telefono. Ti chiameremo non appena un operatore sarà disponibile.

Lasciaci il tuo numero di telefono. Ti chiameremo non appena un operatore sarà disponibile.


Laissez-nous votre numéro de téléphone. Nous vous appellerons dès qu’un de nos conseillers sera disponible.

Laissez-nous votre numéro de téléphone. Nous vous appellerons dès qu’un de nos conseillers sera disponible.