Fibrotubi

Eterinox - MAT Series Stainless Steel and Copper Air Gap

Sistema camino con intercapedine ad aria 10 + 10 mm

Technical Data
Material specification
Internal diameter (mm)*: 80•100•120•140•160•180•200•230
Diametro interno (mm)*: 80•100•120•140•160•180•200•230
Inner wallNominal thickness: 0.5 mm

Grade 1.4404 (AISI 316L stainless steel)

Insulation: 10mm air gap, with wall thermal resistance at 200°C equal to a dry air conductivity of 0.026 m²K/W (300 K, 100 kPa).
Sealing ring: Profiled ring gasket with three sealing lips in black silicone, compliant with UNI EN 14241-1
Roughness: average value 1 mm
General information
InstallationInternal: Yes

External: YES – resistant to rainwater penetration.

Applications: Ducts, chimneys, flue pipes, connectors, and flue systems connected to forced-air boilers, atmospheric and pressurized boilers, type B and C appliances, condensing units, fireplaces, stoves, kitchen hoods, ovens, and ventilation ducts
Permitted fuelsT200: Gas, Diesel, LPG, Pellet

T600: Gas, Diesel, LPG, Pellet, and Wood

Storage: In environments where the atmosphere is non-corrosive
Product warranty: In accordance with Directive 99/44/EC
Hazardous substances: None
Freeze–thaw resistance: Compliant with UNI EN 1856-1
Accidental contact: Protective shielding is required when the wall surface temperature exceeds 70°C
Storage: Do not store the material near ferrous materials; environments must be dry and protected from weather exposure
Limitations of use: The use of stainless steel flue systems is not recommended in environments such as laundries, dry cleaners, furriers, printing facilities, beauty salons, or in any areas where halogenated or chromated vapors are present
Product designation according to standard EN 1856-2: Chimney system.
Standard number: EN 1856-1
Temperature rating
T200
Pressure rating
P1
Condensate resistance
W
Corrosion resistance
V2
Internal wall thickness
L50050
Fire resistance from the inside and distance from combustible materials: O (30) M.
Product designation according to EN 1856-2 standard: Flue gas duct
Standard number: EN 1856-1
Temperature rating
T600
Pressure rating
N1
Condensate resistance
D
Corrosion resistance
V2
Internal wall thickness
L50050
Fire resistance from the inside and distance from combustible materials: G (600) M.
Performance requirements according to the designation
Temperature levelT200

T600

Operation with nominal flue gas temperature lower than 200°C

Operation with nominal flue gas temperature lower than 600°C

Pressure levelP1

N1

Operation with positive and negative pressure up to 200 Pa.
Permissible leakage less than 0.006 l/m²

Operation with positive and negative pressure up to 40 Pa.
Permissible leakage less than 2.0 l/s·m²

Condensate resistanceW

D

Operation with wet and dry flue gases

Operation with dry flue gases

Corrosion resistance
V2 – suitable for operation with gas, diesel oil, LPG, pellets, and wood.
Internal wall specification
L501.4404 (Stainless steel AISI 316L)
Internal wall thickness
050 – nominal thickness 0.5 mm
Internal fire resistanceO

G

No internal fire resistance

Internal fire-resistant

Distance from combustible materials(30)

(600)

(30) = minimum 30mm.

(600) = minimum 600mm.

INSTALLATION INSTRUCTIONS

  • Position the components as indicated by the arrow stamped on the label and shown on the piece.
  • When using T200_P1_W, place the sealing ring in the appropriate seat located in the female socket.
  • The sealing ring must be positioned with the three lips facing towards the inside of the pipe.
  • To prevent damage and facilitate insertion, talc or soap must be used.
  • For use at T600_N1_D, use the product without the sealing ring.
  • After connecting the components, fit and tighten the appropriate locking clamp at each joint.
  • Respect compression loads and non-vertical installation requirements.
  • Avoid the accumulation of condensate or soot, which may cause corrosion. Also avoid horizontal sections and, in any case, install the elements with the longitudinal weld facing upwards (3% slope).

ESSENTIAL CHARACTERISTICS


Wind load resistance:

  • Distance between wall brackets: 2 m.
  • Free length from the last bracket: 1.5 m.

Compression resistance:

  • Maximum load of linear elements: 12 m.
  • Maximum load of 90° straight fitting: 12 m.
  • Maximum load of wall-mounted chimney support: 5 m.

Note: The values above refer to the worst-case condition. For more information, see the Mechanical Resistance Table.

Tensile and bending resistance (straight elements):

  • Maximum tensile load (connection means of chimney elements and fittings): 3 m.
  • Non-vertical installations: max. 45°.
  • Non-vertical installations: distance between wall chimney supports = 2 m

Tensile and bending resistance (non-linear elements):

  • Non-vertical installations: NPD

FLUE SYSTEM MAINTENANCE


Scheduled maintenance carried out by qualified personnel:

  • Unless otherwise required by regulations or agreed with users, the following maintenance intervals are recommended:
    • Gaseous fuels: once per year;
    • Liquid fuels: once every 6 months;
    • Solid fuels: once per month.
  • Cleaning using a soft plastic brush or sponge of the flue pipe, the technical compartment for air supply and ventilation of the ducts, the inspection connection, the chimney cap; checking the free flow of flue gases and condensate, etc.

Contact us

Request information or a customized quote

"*" indicates required fields

Dati personali*

Lasciaci il tuo numero di telefono. Ti chiameremo non appena un operatore sarà disponibile.

Lasciaci il tuo numero di telefono. Ti chiameremo non appena un operatore sarà disponibile.


Laissez-nous votre numéro de téléphone. Nous vous appellerons dès qu’un de nos conseillers sera disponible.

Laissez-nous votre numéro de téléphone. Nous vous appellerons dès qu’un de nos conseillers sera disponible.