| Material specification: Internal diameter (mm): 50•60•80•100•125•160•200•250•315 | |
| Inner wall | Minimum nominal thickness: 1.5mm
Homopolymer polypropylene quality |
| Wall thermal resistance m²K/W at 200°C: Without insulation = 0.00 | |
| Sealing ring: Profiled ring gasket with three sealing lips in black silicone, compliant with UNI EN 14241-1 | |
| Roughness: average value 1 mm |
Eterinox - PPS Series
Condensation in Polypropylene.
- PPS Series rigid and flexible single-wall in Polypropylene.
- The predominant color of the line is white.
- Certified product for condensing generators (T120°)
- Sealing ring certified according to EN 14241-1
- Complete product range
Technical Data
| General information | |
| Installation | Internal: Yes
External: NO, does not resist rainwater penetration and UV rays. |
| Applications: Ducts, chimneys, flue channels, collectors, and chimneys connected to forced-air, atmospheric, pressurized boilers, type B, C appliances, condensing units, kitchen hoods, ovens, and ventilation ducts. | |
| Allowed fuels: T120 Gas, LPG, and Diesel with a sulfur content of =0.2% by mass. | |
| Storage: In environments where the atmosphere is non-corrosive | |
| Product warranty: In accordance with Directive 99/44/EC | |
| Hazardous substances: None | |
| Frost – Thaw resistance: Requirement not met. | |
| Accidental contact: Protective shielding is required when the wall surface temperature exceeds 70°C | |
| Storage: Do not store the material near ferrous materials; environments must be dry and protected from weather exposure | |
| Usage limits: Environments such as laundries, dry cleaners, furriers, printing shops, cosmetic salons, or places where halogen or chromate vapors are present. | |
Features
| Product designation according to the EN 1447-1 standard: Chimney system. | |
| The number of the standard is EN 1447-1. | |
| Temperature level: T120. | |
| Pressure level: P1/H1. | |
| Condensate resistance W | |
| Corrosion resistance: 2. | |
| Luogo di installazione | I |
| Fire resistance from the inside and distance from combustible materials: O(20). | |
| Fire reaction: D. | |
| Wall class: L. |
| Performance requirements according to the designation | ||
| Temperature level T120 — operation with a nominal flue gas temperature below 120 °C. | ||
| Pressure level | P1
H1 | Operation with positive and negative pressure up to 200 Pa. Permissible leakage less than 0.006 l/m²
Operation with positive and negative pressure up to 5000 Pa. Acceptable leakage less than 0.006 l/sm². |
| Operation with positive and negative pressure up to 5000 Pa. Acceptable leakage less than 0.006 l/sm². | ||
| Corrosion resistance: V2. Operation with Gas, LPG, and Diesel with a sulfur content ≤ 0.2% by mass. | ||
| Installation location: Isolated inside buildings. | ||
| Fire reaction: D. The scale ranges from F (products that cannot be classified as fire-resistant) to A1 (products that do not contribute to any phase of the fire). Class D products can withstand a small flame for a short period without substantial propagation. | ||
| Wall class: L, without external protection. | ||
| Fire resistance from the inside: O, does not resist fire from the inside. | ||
| Distance from combustible materials: (20)(20) = minimum 20mm. | ||
Installation
INSTALLATION INSTRUCTIONS
- Place the elements with the female socket facing upwards.
- Use the appropriate sliding connector for the male-female joint, and for horizontal installations, always maintain an inclination of 3°.
- Respect compression loads and non-vertical installation requirements.
ESSENTIAL CHARACTERISTICS
Wind load resistance:
- Distance between wall brackets: NPD m
- Free length from the last bracket: 3 meters.
Compression resistance:
- Maximum load for linear elements: 30 meters.
- Maximum load for 90° straight connector: 30 meters.
- Maximum load for wall-mounted chimney support: 30 meters.
Tensile and bending resistance (straight elements):
- Maximum tensile load (means of connection of elements and chimney fittings): NPDm.
- Non-vertical installations: NPD
- Non-vertical installations: distance between wall chimney supports = NPD (No Performance Determined)
Tensile and bending resistance (non-linear elements):
- Non-vertical installations: NPD
FLUE SYSTEM MAINTENANCE
Scheduled maintenance carried out by qualified personnel:
- Unless otherwise required by regulations or agreed with users, the following maintenance intervals are recommended:
- Gaseous fuels: once per year;
- Liquid fuels: once every 6 months;
- Cleaning using a soft plastic brush or sponge of the flue pipe, the technical compartment for air supply and ventilation of the ducts, the inspection connection, the chimney cap; checking the free flow of flue gases and condensate, etc.